Guide specification
Tubing Bundle Specification: Sample Text for Project Specs
Published:
Engineers who write an instrument or analyser specification need a clause set for traced tubing. This page gives one for factory-assembled tubing bundles: electric heat traced, steam traced and pre-insulated. Copy it into your project specification, choose the options in square brackets, and attach your line schedule. The same text is available as an editable Word file.
Request a quoteHow to use this template
- Square brackets [ ] mark a choice or a value for the specifier. Delete what does not apply.
- This is a general template. It does not describe one maker's product and it is not a statement of what any supplier can deliver. Ask each bidder to confirm clause by clause.
- Attach your line schedule or the tubing bundle data sheet so that every bundle has its own design basis.
1. Scope
- This specification covers factory-assembled tubing bundles for instrument impulse lines, analyser sample lines and small-bore process lines. Bundles are [electrically heat traced] [steam traced] [pre-insulated without tracing].
- Each bundle shall be supplied as one continuous length made up of the process tube(s), [the tracer,] thermal insulation and an extruded outer jacket.
- Tracing and insulation applied in the field to individual tubes is not acceptable for the lines in the line schedule unless the purchaser agrees in writing.
2. Reference documents
- The latest edition applies unless a date is given. Where documents conflict, the purchaser decides.
- Electric trace heating in explosive atmospheres: IEC/IEEE 60079-30-1 (general and testing requirements) and IEC/IEEE 60079-30-2 (application guide for design, installation and maintenance).
- [North American projects: IEEE 515.]
- Certification scheme for electrical equipment in hazardous areas: [IECEx] [ATEX Directive 2014/34/EU] [other scheme required at the site].
- Process tube standard: [ASTM A269] [ASTM A213] [EN 10216-5] [other].
- Material inspection documents: [EN 10204 type 3.1].
3. Design basis to be stated by the purchaser for each bundle
- Fluid in the process tube(s), and the temperature to be maintained [or freeze protection only].
- Highest temperature the bundle will be exposed to, for example during steam-out, with the heating [on] [off].
- Minimum ambient temperature and design wind speed.
- Area classification: [zone or division], gas group and temperature class.
- Electric tracing: supply voltage and frequency. Steam tracing: steam pressure and temperature at the bundle.
- Length of each run and the longest single circuit.
- Site environment for the jacket: sunlight, chemicals, wash-down, burial or cable tray.
4. Construction
- Process tubes: [number] tube(s), outside diameter [value], wall thickness [value], material [316/316L stainless steel, seamless] [316/316L stainless steel, welded] [copper] [PTFE] [PFA] [other].
- Process tubes shall run the ordered length without joints inside the bundle wherever the coil length allows. Any joint shall be declared in the offer.
- [Tubes shall carry the inert internal coating named in the data sheet.]
- Electric tracing: heating cable type [self-regulating] [constant wattage] [power-limiting] [series resistance]. The cable shall be certified by a recognised body for the stated area classification and temperature class.
- The supplier shall select the heating cable output from a heat-loss calculation for the design basis. The circuit length shall stay within the cable manufacturer's limit for the stated voltage and start-up temperature.
- Steam tracing: tracer tube [copper] [stainless steel], outside diameter [value]. [Heavy tracing: tracer in direct contact with the process tube.] [Light tracing: tracer separated from the process tube.]
- Thermal insulation shall be non-hygroscopic. The supplier shall set the thickness so that the maintain temperature and the jacket surface limit are both met.
- Outer jacket: continuous extruded [flame-retardant, UV-resistant PVC] [TPU] [TPE] [polyamide], suitable for the stated ambient range and environment. Colour black unless stated.
- The outer jacket surface shall not exceed [60 °C (140 °F)] at design conditions, for personnel protection.
5. Calculations to be submitted with the offer
- Heat-loss calculation for each bundle type at the minimum ambient temperature and design wind speed.
- Electric tracing: the maximum sheath temperature compared with the temperature class, and whether it is reached by stabilised design or by a temperature control and limiter.
- Electric tracing: start-up current at minimum ambient temperature, and the recommended circuit protection.
- Steam tracing: the expected tube temperature at the stated steam pressure, for heavy or light tracing as specified.
6. Marking
- The jacket shall be marked along its length with the manufacturer's name, the bundle type or part number [and length marks].
- Each coil or drum shall carry a tag with the purchaser's line or tag number, the bundle part number and the length.
7. Inspection and testing at the factory
- Visual and dimensional check of each coil against the approved data sheet.
- Electric tracing: continuity and insulation resistance test of the heating cable in each coil, to the heating cable manufacturer's instructions and the reference standard. Results shall be recorded.
- [Process tubes: pressure or leak test as stated in the data sheet.]
- Tube ends shall be capped and bundle ends sealed against moisture after testing.
- [The purchaser may witness the tests. The supplier shall give notice of the test date.]
8. Documents
- With the offer: data sheet with a cross-section drawing for each bundle type, the calculations listed above, and a list of deviations from this specification.
- With the delivery: material inspection documents for the process tubes, the heating cable certificate(s), factory test records, and installation instructions that state the minimum bending radius, the supports and the end sealing method.
9. Packing and delivery
- Bundles shall be delivered in coils or on drums, not bent below the minimum bending radius.
- Bundle ends shall stay sealed and tube ends capped until installation.
- Each package shall be marked with the purchase order number, the tag numbers inside and the gross weight.
10. Installation accessories, where ordered
- End seal and termination kits for each bundle end.
- Electric tracing: power connection kits, [splice kits,] and [temperature sensor and controller] suitable for the area classification.
- Steam tracing: tracer connection fittings as stated in the data sheet.
Frequently asked questions
What should a heat traced tubing bundle specification include?
The scope, the reference standards, a design basis for each bundle (maintain temperature, minimum ambient, wind, area classification, voltage or steam pressure), the construction of tubes, tracer, insulation and jacket, the calculations the supplier must submit, marking, factory tests, documents and packing.
Can I use this specification with any supplier?
Yes. It is a general template and names no brand. Ask each bidder to list deviations clause by clause so that offers can be compared.
Which standards apply to electric heat traced tubing in hazardous areas?
IEC/IEEE 60079-30-1 gives the general and testing requirements for electrical resistance trace heating in explosive atmospheres, and IEC/IEEE 60079-30-2 is the application guide for design, installation and maintenance. North American projects also refer to IEEE 515. The heating cable must be certified for the zone or division, gas group and temperature class of the site.
Is a specification the same as a data sheet?
No. The specification sets the rules that apply to every bundle on the project. The data sheet gives the design basis for one bundle: fluid, temperatures, tube sizes, lengths and area classification. Use both together.
Want an offer against your specification?
Send your specification and line schedule. Our engineers will review it against each clause and quote the bundles.
Request a quote